USA Cummins NTA855-G1A engine diesel generator 220kw standby power 312kva genset 50hz 60hz
1. SPECIFICATIONS OF GEN-SET | ||
1.1 | Set Model | PF-CCS312 |
1.2 | Prime at 50HZ, 40℃ ambient | 220KW 275KVA |
1.3 | Standby at 50HZ, 40℃ ambient | 250KW 312KVA |
1.4 | Rated Gen-set output | 230/400V 50Hz |
1.5 | Rated Relative humidity | ≤ 60 % |
1.6 | Dimension (L×W×H) | 4500×1440×2100mm |
1.7 | Weight | 4555kg |
1.8 | Fuel consumption 100% prime load | 70L/h |
1.9 | Total heat radiated to ambient | 66KW |
1.10 | Noise Level at 7m (Normal/Super) | 75/70dB |
1.11 | Structure of Gen-set | The Gen-set adopt integrative structure, engine is fix on high strength steel basic frame, anti vibration instrument between the engine and basic frame, cooling fan have protecting cap, control cabinet and circuit breaker installed on Gen-set. |
1.12 | Control system (Optional) | Basic control panel or Advanced control panel with automatically start-up function and other function. |
2. SPECIFICATIONS OF ENGINE | ||
2.1 | Engine Brand | Cummins |
2.2 | Engine Model | NTA855-G1A |
2.3 | Governor/Class | Electrical |
2.4 | Cylinder NO. | 6 |
2.5 | Engine build | Line |
2.6 | Fuel spray pattern | PT direct injection |
2.7 | start-up method | 24V, electric |
2.8 | Aspiration | Turbocharged/Aftercooled |
2.9 | Cooling mode | Radiator cooled (enclose water) |
2.10 | Bore and stroke | 140×152 mm |
2.11 | Compression ratio | 14.5:1 |
2.12 | Displacement | 14L |
2.13 | Engine Prime Power at 1500rpm | 261KWm |
2.14 | Engine Standby Power at 1500rpm | 291KWm |
2.15 | Battery capacity | 127A/hr |
2.16 | Starting/Min temperature | 7℃ |
2.17 | Lubrication oil capacity | 36.7L |
2.18 | Coolant capacity - radiator and engine (40℃) | 49L |
2.19 | Exhaust temp - full load prime | 450℃ |
2.20 | Exhaust gas flow - full load prime | 3500m3/h |
2.21 | Exhaust gas back pressure max | 76mmHg |
2.22 | Air flow - radiator (40℃ ambient) | 6.8 m 3/s |
2.23 | Pusher fan head (duct allowance) 40℃ | 13mmH 2O |
2.24 | Air intake - engine- full load prime | 1206m3/h |
2.25 | Standard Air intake temp | 25℃ |
2.26 | Fuel type | #0 Diesel (Natural temperature) |
2.27 | Filter system | Adopt whole changeable lubricating oil, fuel filter and air filter |
2.28 | Exhaust system | Adopt industrial high efficiency muffler and ripple pipe |
3. SPECIFICATIONS OF ALTENATOR | ||
3.1 | Alternator Model | Stamford/HC1444D |
3.2 | Alternator Type | A.C. Synchronous |
3.3 | Rated Voltage | 230/400V |
3.4 | Rated Frequency | 50HZ |
3.5 | Rated speed | 1500 RPM |
3.6 | Voltage regulation mode | Auto |
3.7 | Alternator voltage regulation | ±0.5% |
3.8 | Exciting mode | Brushless self exciting |
3.9 | Power factor | 0.8 (lagging) |
3.10 | Phase & wires | 3 phase 12 wires |
3.11 | Rated currency | 433.0A |
3.12 | Efficiency | 0.93 |
3.13 | Insulation class | H |
3.14 | Protection class | IP21 |
3.15 | Single load step to NFPA110 | 100% |
3.16 | Standards | IEC34-1 |
3.17 | Max. Ambient Temperature | 40℃ |
3.18 | Min. Ambient Temperature | - 20℃ |
3.19 | Max. altitude | 1000m |
3.20 | Weight | 915.5kg |
Heavy duty world class brand industrial diesel engine:
a) Compact size
b) Economic and easy start in cold weather
2) World class brand-Stamford alternator:
a) Optional permanent magnet generator (PMG) system provides
constant excitation under all conditions
b) Easy paralleling with mains or other generators, standard 2/3 pitch
winding avoids excessive neutral currents
c) Dynamically balanced rotors with sealed-for life ball bearings and
single construction
d) Class "H" insulation system
e) Wide range of flange adapters and disc couplings
f) Conforms to all leading industrial and marine standards
ATS-Automatic Transfer Switch, when the city power supply failure, the genset will be running automatically within few minutes.
Our normal ATS is bulit inside,but outside ATS box is optional
Testing Items of Power Friend Genset:
1) Parts fault testing
2) Fue tank pressure testing
3) Bolt tightening torque testing
4) Painting thickness testing
5) Voltage bearing and insultion testing
6) Noise testing
7) Loading testing: All qualified generator sets are subjected to a comprehensive performance test which inclides 0% load, 25% load, 50% load, 75% load, 100% load and 110% load and to check, verify that all control systems, alarm and shut-own protection.
Guarantee:
1) Guarantee Period: One year or 1000 running hours, depends on whichever comes first.
2) During the guarantee period, the spare-parts will be sent through your shipping agency in China.
3) Spare-parts can also be sent by air express.
4) 24 hours service hotline is available for customers.
If you are interested, please contact with us at any time!